Mar 04, 2026
Content
To size a diesel generator, calculate the total running wattage of all loads it must power simultaneously, add the largest single-motor starting surge (typically 3× its running wattage), apply a 20–25% capacity buffer, then derate for altitude and ambient temperature. The result is the minimum generator kVA rating you need. For example: a facility with 40 kW of running loads, a 15 kW motor as the largest single starter (requiring a 45 kW surge), and operations at 1,500m altitude needs a generator rated for at least 68–75 kVA after all adjustments. Undersizing causes overload trips and engine damage; oversizing wastes fuel and causes wet-stacking in diesel engines. This guide walks through every step of the sizing process with worked examples, load tables, and correction factors.
The foundation of generator sizing is a complete load inventory. Missing even one large load — a compressor, an elevator motor, or a central air conditioning unit — can invalidate the entire sizing calculation. Organize loads into three categories based on their electrical behavior:
For each load, record the nameplate running watts (or kW), voltage, and phase (single-phase or three-phase). If nameplate data is unavailable, use the amperage rating and calculate: Watts = Volts × Amps × Power Factor (use 0.85–0.90 for most motors if power factor is not stated).
Sum all running watts for every load that will operate simultaneously. Do not include loads that are never used at the same time — a standby generator powering a building after a utility outage does not need to serve both the chilled water plant and the heating system simultaneously if they operate in different seasons. However, be conservative: include loads that could theoretically overlap even if unusual.
When an electric motor starts, it draws a locked-rotor current (LRC) that is typically 3 to 7 times its full-load running current. For generator sizing, this surge is expressed as starting watts — the instantaneous power demand at motor start. The most commonly used multipliers by motor type are:
The generator must handle the scenario where the largest motor starts while all other running loads are already drawing power. The critical calculation is: Generator sizing load = (Total running watts of all loads) + (Starting surge of the largest single motor − its running watts). This represents the peak instantaneous demand at the moment the largest motor starts.
Consider an office building requiring standby power for:
Total running load: 12 + 8 + 15 + 10 + 7.5 = 52.5 kW
Largest motor starting surge: Elevator motor at 45 kW starting − 15 kW running = 30 kW additional surge demand
Peak instantaneous demand: 52.5 + 30 = 82.5 kW
Generator capacity is rated in kVA (kilovolt-amperes) — apparent power — rather than kW (kilowatts) — real power. The relationship is:
kVA = kW ÷ Power Factor
Most diesel generators are rated at a power factor of 0.8 lagging — this is the standard assumption unless otherwise specified. A generator rated 100 kVA at 0.8 power factor delivers 80 kW of real power. This means you must divide your kW requirement by 0.8 to find the required kVA rating.
Continuing the worked example:
If your load is predominantly resistive (heaters, lighting) with very few motors, the actual power factor may be closer to 0.9–1.0, and dividing by 0.8 is overly conservative. If your load is predominantly inductive motors, the actual power factor may be 0.7 or lower, and a 0.8 assumption may under-size the generator. For precision sizing, measure or calculate the weighted average power factor across all loads.
Running a diesel generator at 100% of rated capacity continuously causes excessive thermal stress, accelerates wear, and leaves no margin for load additions or calculation errors. Industry practice is to operate diesel generators at 70–80% of rated capacity at full running load, leaving 20–30% headroom.
Apply the headroom factor by dividing the calculated kVA requirement by the target loading fraction:
Continuing the example at 80% loading: 103 kVA ÷ 0.80 = 129 kVA minimum rated generator. The nearest standard generator size above this is typically a 150 kVA unit.
A note on minimum loading: diesel engines also have a minimum load requirement of 30–40% of rated capacity. Running a diesel generator below this threshold for extended periods causes wet-stacking — incomplete combustion deposits unburned fuel and carbon in the exhaust system and cylinders, increasing maintenance costs and reducing engine life. If your expected running load is frequently below 30% of the generator's rating, the unit is oversized and you should select a smaller generator or implement load banking (connecting artificial resistive load to maintain minimum engine loading).
Diesel generator power output is rated at standard conditions: sea level (0m altitude), 25°C (77°F) ambient temperature, and 30% relative humidity per ISO 8528-1 or SAE J1349. Operating above sea level or in high ambient temperatures reduces the air density reaching the engine, reducing combustion efficiency and power output. The generator must be derated — its effective output is less than the nameplate rating, so the nameplate rating must be higher than calculated.
The standard derating rule for naturally aspirated diesel engines is approximately 3–4% power loss per 300m (1,000 ft) above sea level. Turbocharged engines derate less — typically 1–2% per 300m — because the turbocharger compensates for reduced air density up to its design limit, after which derating increases sharply. Always use the manufacturer's specific derating curves; the values below are representative:
| Altitude | Derating Factor (Turbocharged) | Derating Factor (Naturally Aspirated) | Effective Output of 100 kVA Unit |
|---|---|---|---|
| Sea level (0m) | 1.00 | 1.00 | 100 kVA |
| 500m (1,640 ft) | 0.98 | 0.94 | 98 kVA / 94 kVA |
| 1,000m (3,280 ft) | 0.96 | 0.88 | 96 kVA / 88 kVA |
| 1,500m (4,920 ft) | 0.94 | 0.82 | 94 kVA / 82 kVA |
| 2,000m (6,560 ft) | 0.91 | 0.76 | 91 kVA / 76 kVA |
| 3,000m (9,840 ft) | 0.85 | 0.64 | 85 kVA / 64 kVA |
Above the standard 25°C rating temperature, generators derate at approximately 1% per 5.5°C (10°F) above 25°C for most turbocharged engines. In a tropical environment with a 45°C peak ambient temperature (20°C above standard), expect an additional 3–4% power reduction. Combined altitude and temperature derating is multiplicative — both factors apply simultaneously.
To find the required nameplate kVA after derating: Required nameplate kVA = Required effective kVA ÷ (Altitude factor × Temperature factor)
Example: A 129 kVA effective requirement at 1,500m altitude (factor 0.94) and 40°C ambient (factor 0.97) requires: 129 ÷ (0.94 × 0.97) = 129 ÷ 0.912 = 141 kVA nameplate minimum, so select the next standard size: 150 kVA.
| Load Type | Typical Running Watts | Starting Surge Multiplier | Notes |
|---|---|---|---|
| Incandescent / halogen lighting | Nameplate watts | 1× (no surge) | Purely resistive; PF = 1.0 |
| LED lighting (with driver) | Nameplate watts | 1–1.5× (brief inrush) | Non-linear load; may need harmonic-rated alternator |
| Central air conditioner (DOL) | 2,000–5,000 W per ton | 3× | Most common oversizing driver in residential sizing |
| Air conditioner (inverter/VFD) | 2,000–5,000 W per ton | 1.1–1.3× | Dramatically reduces generator sizing; preferred for generator applications |
| Water pump (DOL, 1–5 HP) | 750–3,750 W | 3× | Submersible pumps often have higher surge (up to 5×) |
| Refrigerator / freezer | 150–800 W | 2–3× | Compressor cycling creates repeated surges throughout operation |
| Electric motor (industrial, DOL) | Nameplate kW | 3–6× (verify with motor spec) | Largest single sizing factor in industrial applications |
| Electric motor (with soft starter) | Nameplate kW | 1.5–2× | Reduces peak surge; check soft starter compatibility with generator |
| UPS system | Input kVA × 0.9 efficiency | 1–1.5× | Non-linear load; size generator at 1.5–2× UPS kVA for harmonic margin |
| Welding equipment | Duty cycle dependent | 1–2× | Size for peak arc demand; inverter welders are more generator-friendly |
| Electric resistance heater | Nameplate watts | 1× (no surge) | Pure resistive; high kW demand but excellent power factor |
Diesel generators are sold with multiple rating classifications that define how hard and how long the engine can sustain a given output. Using a generator beyond its intended rating class causes premature engine failure. The four main ISO 8528 rating classes are:
A generator marketed as "100 kVA Standby / 90 kVA Prime" has two different power limits depending on how it is used. For a hospital backup generator used only during power outages, the 100 kVA standby rating applies. For a mining camp generator running continuously as the only power source, the 90 kVA prime rating governs — and the sizing calculation must use 90 kVA as the reference, not 100 kVA.
Generators above approximately 15–20 kVA are almost always three-phase (3Φ) because three-phase power provides more efficient power delivery and is required for three-phase motors. When sizing a three-phase generator for a mixed load (some three-phase motors plus single-phase loads), phase balance becomes a critical consideration.
Three-phase generators are rated for balanced loads — equal power on each phase. If single-phase loads are distributed unevenly across the three phases, the most heavily loaded phase limits total generator output and can cause voltage imbalance that harms motors and electronics. Most generator manufacturers specify that single-phase load imbalance between any two phases should not exceed 25% of the generator's rated current per phase.
When preparing your load list for a three-phase generator, assign each single-phase load to a specific phase and verify that no phase carries more than approximately 1/3 of total load + 12.5% of total kVA. In practice, distribute loads as evenly as possible and verify balance with an electrician during installation.
Non-linear loads — UPS systems, variable frequency drives, switch-mode power supplies, and battery chargers — draw non-sinusoidal current that introduces harmonic distortion into the generator's voltage output. This harmonic content causes additional heating in the alternator windings and can interfere with the generator's automatic voltage regulator (AVR), causing voltage instability.
The industry guideline for sizing generators feeding predominantly non-linear loads:
A manufacturing workshop in a mountainous region at 1,200m altitude with a peak ambient temperature of 38°C requires a prime power generator for the following loads:
| Load Description | Running Watts (kW) | Starting Surge (kW) | Notes |
|---|---|---|---|
| Workshop lighting (LED) | 6 kW | 6 kW | No surge |
| Air compressor (DOL, 15 kW) | 15 kW | 45 kW | Largest motor — drives sizing |
| CNC machine (with VFD) | 18 kW | 22 kW | VFD reduces surge to 1.25× |
| Ventilation fans (3 × 2.2 kW) | 6.6 kW | 20 kW | 3× surge each; stagger starts if possible |
| Office equipment / UPS (10 kVA) | 8 kW | 10 kW | 1.25× for non-linear load |
| TOTALS | 53.6 kW | — | — |
Sizing calculation: